LZZW-12 Current Transformer 1
LZZW-12 Current Transformer 1

LZZW-12 Current Transformer

The supporting-type current instrument transformers LZZW-12 are fully enclosed and cast in epoxy resin. The transformers are designed for electric power systems of 50Hz/60Hz rated frequency and 12kV rated voltage.They are used for outdoor mounting. The performances of the products meet standards IEC60044-1 and GB1208-2006. The products are applied to metering electric energy,voltage controlling and relay protection.

    oops...!

    no product data.

    Go to homepage

    Execution Standards

    图片1 (3)

    technical specification

    1.  Ambient temperature:-25℃~40℃;

    Note: By customize manufacture,the ambient temperature can be as low as-40℃.

    2.Altitude:≤1000m;

    3. Pollution class:IV;



    ● Rated insulation level: 12/42/75kV.

    Rated secondary winding current:5A/1A.

    The rated current and accuracy class are displayed in the table below.

    Partial discharge (PD) level meets standard IEC60044-1.

    When transformer is working with computer, the lower limit of secondary load can be as low as 1VA for accuracy class 0.2 and0.5.


    1502244698523039934 - 副本
    1502244698523039934 - 副本

    Structure feature

    1. Cores and windings are cast together in epoxy resin.

    2. The transformer cores are manufactured of high-grade magnetic material.

    3. The transformer is fixed to the base plate by four screws.

    4. The bolted earthed clamp is located on the transformer base plate.

    5. The secondary terminals are covered with a protective cover.

    6. As the high level of insulation,it can work normally in damp and Pollution II condition.

    7. The cores and windings are cast together.

    8. Three optional ways of installation,correspondent to product version of A/B/C.

    9. The outlet terminals of theprimary winding and secondary winding, are respectively marked as P1,P2 and S1,S2.

    10. The case that, primary current runs from P1 to P2 and secondary current flows from S1 to S2 through external circuit, is called subtractive polarity. The secondary circuit should not be open, when primary current is flowing. Otherwise,a high voltage will be generated.

    11. The transformers are equipped with primary winding and secondary windings.The windings are fixed to the iron core bar by casting,

    12. For the two secondary windings,the first one is for either measuring or protecion purposes; the other is for being connected into an open-delta connection in a three-phase system.

    13. The outlet of the primary winding is insulated from the earth to a correspondent level.

    14. The secondary terminal board is covered with a transparent cover made of plastic.

    Technical specification

    Rated
    voltage
    ratio(V)

    Accuracy
    classes
    combination

    Rated output(VA)

    1s thermal
    current
    (kA)

    Rated
    dynamic
    current(kA)

    0.2S

    0.2

    0.5S

    0.5

    10P10

    50

    0.2S
    0.5S
    0.2
    0.5S
    10P10

    10

    10

    15

    15

    15

    9

    22.5

    75

    15

    37.5

    100

    18

    45

    150

    25

    62.5

    200

    28

    70

    300

    40

    100

    400

    40

    100

    500

    60
    60
    60

    130
    130
    130

    600

    630

    Outline dimension

    未标题-1 (4)
    未标题-1 (4)
    Drop us a line or just say Hello!
    Just leave your email or phone number in the contact form so we can send you a free quote for our wide range of products!
    Related Products
    no data
    With a variety of operating characteristics and the principle of small profits, has won the trust of our customers and praise.
    Mobile: 86- 189 0689 2820
    Address: F4-19037-6#, Yiwu Intl Trade Mart, Yiwu Jinhua, Zhejiang, China (Mainland)
    Copyright © 2025 Yiwu Sasun Electrical Co.,Ltd. - www.chinasasun.com | Sitemap | Privacy policy
    Customer service
    detect