Min. Order: | 10 Set/Sets |
---|---|
Trade Term: | FOB |
Payment Terms: | L/C, T/T |
Place of Origin: | Zhejiang, China (Mainland) |
Means of Transport: | Ocean |
Production Capacity: | 1000SET |
Packing: | WOODEN CASES |
Delivery Date: | 25DAYS | RATED VOLATAGE: | 12KV |
---|---|---|---|
RATED CURRENT: | 630A | TYPE: | INDOOR |
MODEL: | LOAD BREAKE SWITHCH |
FKN-120D/630-20 AC indoor high voltage switchgear Description
serial no. | Item | unit | FKN-12D/630-20 | FKN-12R.D/125-31.5 |
1 | rated voltage | KV | 12 | |
2 | rated frequency | HZ | 50 | |
3 | rated current | A | 630 | 125 |
4 | Lightning impulse withstand voltage | KV | ||
5 | Power frequency withstand voltage | KV | ||
6 | Rated thermal stability current | KA | 20(4S) | |
7 | Rated dynamic current | KA | 50 | |
8 | rated closing current(peak value) | KA | 50 | - |
9 | rated short circuit breaking current | KA | - | 31.5 |
10 | rated displace current | KA | - | 1.5 |
11 | max breaking current(reference value) | KA | 1.8 | |
12 | breaking no-load transformer capacity | KVA | 1250 | |
13 | Rated cable charging current | A | 10 | |
14 | Rated load current breaking times | times | >100 | |
15 | The impactor trigger switch tripping time | S | - | >0.06 |
16 | Earthing switch thermal stability current | KA | 20(2s) | 20(2s) |
17 | Earthing switch thermal stability current(peak value) | KA | 50 | 50 |
18 | Motor operating power supply voltage | V | AC220\DC48 |
packing picture
Category: Disconnector Switch & Load Break Switch